.. these roles are defined to use custom css classes .. role:: orange .. role:: blue .. role:: yellow .. role:: red .. role:: green .. role:: white-cell Vault-1 Laser Interlock System Testing Protocol =============================================== The purpose of this testing procedure if the Verify the functionality of the Vault-1 laser interlock system including arming Vault-1 as a laser lab, and arming the Pharos system. Additionally, the administrative override on the Pharos and Dira enclosures will be tested. ----- Starting Conditions ------------------- #. VIEWMARQ in Vault-1 Control displays :green:`LASER SAFE`. #. Vault-1 beacon stacks show :green:`green` LED on. - Vault-1 Control. - Vault-1 east wall. - Pharos LASER ENCLOSURE INTERLOCK protocase. - Dira LASER ENCLOSURE INTERLOCK protoacse. #. Vault-1 entry keypad LED for :green:`RELEASED` is on. #. Vault-1 laser warning modules show :green:`LASER SAFE`. - Vault-1 Control. - Pharos enclosure south wall. - Pharos enclosure north wall. - Dira LASER ENCLOSURE INTERLOCK protoacse. #. Laser control module shows :green:`LASER SAFE`. When the Vault-1 door is open, the module shows :orange:`ACCESS`. #. Laser warning module on the Pharos LASER ENCLOSURE INTERLOCK protocase shows :red:`DANGER LASER ON`. #. None of the laser E-stops are engaged or glowing. - Pharos enclosure east wall. - Pharos enclosure north wall. - Dira enclosure east wall. - Dira enclosure west wall. #. All room interlock modules LED for :green:`ROOM DISABLED (READY TO ARM)` is on. - Vault-1. - Pharos enclosure. #. Local interlock modules LEDs for :green:`LOCAL CONTACTS DISARMED`, and :green:`ROOM NOT ARMED - LOCAL CONTACTS CANNOT ARM` is on. - Pharos enclosure. - Dira LASER ENCLOSURE INTERLOCK protocase AUX #1. - Dira LASER ENCLOSURE INTERLOCK protocase AUX #2. #. Local interlock modules LEDs for :green:`LOCAL CONTACTS DISARMED` are on. - Pharos LASER ENCLOSURE INTERLOCK protocase CONTROL #1. - Pharos LASER ENCLOSURE INTERLOCK protocase CONTROL #2. #. Administrative override keys are set to INTERLOCK, with STATUS LED :green:`green`. - Pharos LASER ENCLOSURE INTERLOCK protocase INTERLOCK OVERRIDE. - Dira LASER ENCLOSURE INTERLOCK protocase INTERLOCK OVERRIDE. #. Both enclosures are closed, and the Door / Curtain Monitors should show :green:`CLOSED`. - Pharos enclosure. - Dira enclosure. #. Push before exit buttons is not on. .. figure:: /images/user_docs/Vault-1_laser/Vault-1_VIEWMARQ_safe.jpg :align: center :scale: 20 % **Figure 1:** This is the Vault-1 Control VIEWMARQ display when the system is in a safe state. .. list-table:: :align: center * - .. image:: /images/user_docs/Vault-1_laser/Vault-1_Control_beacons.jpg :scale: 76 % :align: center - .. image:: /images/user_docs/Vault-1_laser/Vault-1_beacons.jpg :scale: 20 % :align: center - .. image:: /images/user_docs/Vault-1_laser/Pharos_beacons.jpg :scale: 43 % :align: center - .. image:: /images/user_docs/Vault-1_laser/Dira_beacons.jpg :scale: 53 % :align: center * - Vault-1 Control beacon stack. :white-cell:`=========================================================` - Vault-1 beacon stack. :white-cell:`=================================================================` - Pharos LASER ENCLOSURE INTERLOCK protocase beacon stack. :white-cell:`==============================` - Dira LASER ENCLOSURE INTERLOCK protocase beacon stack. :white-cell:`================================` .. table-caption:: **Table 2:** These are the Vault-1 laser interlock system beacon stacks. .. figure:: /images/user_docs/Vault-1_laser/Vault-1_entry_unarmed.jpg :align: center :scale: 20 % **Figure 3:** This is the Vault-1 entry modules when the system is in a safe state. .. figure:: /images/user_docs/Vault-1_laser/Vault-1_unarmed.jpg :align: center :scale: 20 % **Figure 4:** This is the Vault-1 laser control module when the system is in a safe state. .. figure:: /images/user_docs/Vault-1_laser/Pharos_protocase.jpg :align: center :scale: 20 % **Figure 5:** This is the Pharos enclosure laser warning module when the system is in a safe state. .. figure:: /images/user_docs/Vault-1_laser/Dira_protocase.jpg :align: center :scale: 20 % **Figure 6:** This is the Dira enclosure laser warning module when the system is in a safe state. .. figure:: /images/user_docs/Vault-1_laser/laser_e-stop_off.jpg :align: center :scale: 20 % **Figure 7:** This is the laser e-stop button when the system is in a safe state. ----- Arming Vault-1 as a Laser Lab ----------------------------- #. While inside of Vault-1 with the vault door latched, press ARM on the room interlock arming module. It should light the LED for :orange:`ROOM ARMED`, and there will be an audible chime. #. The laser control module shows :red:`DANGER LASER ON`. #. The push to exit button is on. #. The Vault-1 door is magnetically locked. #. The VIEWMARQ display in Vault-1 Control displays :red:`DANGER LASER ON`. #. Vault-1 laser warning modules display :red:`DANGER LASER ON`. #. Entry keypad LED for :red:`INTERLOCKED` is on. #. They in a random pin. The Vault-1 door will not unlock. #. Type in the correct pin and open the Vault-1 door. #. The entry keypad LED for :green:`RELEASED` is on. #. Vault-1 beacon stacks show no LEDs on. - Vault-1 Control. - Vault-1 east wall. - Pharos LASER ENCLOSURE INTERLOCK protocase. - Dira LASER ENCLOSURE INTERLOCK protocase. #. Leave the vault door open for :red:`x seconds` and allow the system to trip. - The Vault-1 laser interlock system should return to its initial conditions. - The Vault-1 room arming module should show :orange:`ROOM CRASHED (CANNOT ARM)`, then :green:`ROOM DISABLED (READY TO ARM)` once the door is closed. .. figure:: /images/user_docs/Vault-1_laser/Vault-1_armed.jpg :align: center :scale: 20 % **Figure 8:** This is the Vault-1 laser control module when the system is armed. .. figure:: /images/user_docs/Vault-1_laser/Vault-1_VIEWMARQ_laser_hazard.jpg :align: center :scale: 20 % **Figure 9:** This is the Vault-1 Control VIEWMARQ display when the system is armed. .. figure:: /images/user_docs/Vault-1_laser/Vault-1_entry_armed.jpg :align: center :scale: 20 % **Figure 10:** This is the Vault-1 entry modules when the system is armed. ----- Arming the Pharos Enclosure and Laser ------------------------------------- #. With the Vault-1 unarmed, arm the room interlock module on the Pharos enclosure. - The room interlock module only lights the LED for :orange:`ROOM ARMED`. - The local interlock module will auto-arm only lights the LED for :orange:`LOCAL CONTACTS ARMED`. - The laser warning control module shows :red:`DANGER LASER ON`. #. Laser E-stops buttons are on. - Pharos enclosure west wall - Pharos enclosure north wall #. The VIEWMARQ in Vault-1 Control will display :green:`LASER SAFE` - :red:`PHAROS ARMED`. #. Beacon stacks show :green:`green` and :blue:`blue` LEDs activated. - Vault-1 Control - Vault-1 east wall - Pharos LASER ENCLOSURE INTERLOCK protocase - Dira LASER ENCLOSURE INTERLOCK protocase #. Change the Pharos LASER ENCLOSURE INTERLOCK protocase INTERLOCK OVERRIDE key from INTERLOCK to OVERRIDE. The STATUS LED remains :green:`green`. Change back to INTERLOCK. #. Rearm Vault-1 as a laser lab. #. The VIEWMARQ in Vault-1 Control displays :red:`DANGER LASER HAZARD - PHAROS ARMED`. #. Beacon stacks show :blue:`blue` LED activated. - Vault-1 Control - Vault-1 east wall - Pharos LASER ENCLOSURE INTERLOCK protocase - Dira LASER ENCLOSURE INTERLOCK protocase .. list-table:: :align: center * - .. image:: /images/user_docs/Vault-1_laser/Pharos_enclosure_unarmed.jpg :scale: 20 % :align: center - .. image:: /images/user_docs/Vault-1_laser/Pharos_enclosure_armed.jpg :scale: 20 % :align: center * - Pharos enclosure when unarmed. :white-cell:`======================================================` - Pharos enclosure when armed. :white-cell:`========================================================` .. table-caption:: **Figure 11:** These are the Pharos enclosure laser warning modules when the system is unarmed and armed. .. figure:: /images/testing_documentation/Vault-1_laser/Vault-1_Control_VIEWMARQ_Pharos_armed_hazard.jpg :align: center :scale: 20 % **Figure 12:** This is the Vault-1 Control VIEWMARQ display when the system is armed. .. figure:: /images/user_docs/Vault-1_Laser/laser_e-stop_on.jpg :align: center :scale: 20 % **Figure 13:** This is the laser e-stop button when the system is armed. ----- Safe Pharos E-Stop Test ----------------------- #. Put the Pharos into a powered down state. #. Arm the Pharos and the Pharos enclosure. #. Press one of the Pharos enclosure laser e-stops. #. Verify that the Pharos power supply is cut off. ----- Administrative Override on the Pharos Enclosure ----------------------------------------------- #. With the Pharos and Vault-1 armed, arm the LOCAL INTERLOCK CONTACT CONTROL modules on the Pharos LASER ENCLOSURE INTERLOCK protocase. - CONTROL #1 - CONTROL #2 #. Open the Pharos enclosure rolling doors. In response: - Pharos LASER ENCLOSURE INTERLOCK protocase laser warning module will display :green:`LASER SAFE`. - The LOCAL INTERLOCK CONTACT CONTROL modules will disarm and display :orange:`LOCAL CONTACTS DISARMED`. - Pharos LASER ENCLOSURE INTERLOCK protocase door monitor will display nothing. - Pharos UV and IR shutters will close. - The Pharos power supply is cut off. #. Rearm the contact controls, and repeat step 2 for all enclosure doors. - East door - North door - South door #. Turn the Pharos LASER ENCLOSURE INTERLOCK protocase INTERLOCK OVERRIDE key from :red:`INTERLOCK` to :red:`OVERRIDE`. The STATUS LED will change to :red:`red`. #. The VIEWMARQ in Vault-1 Control will display :red:`DANGER LASER HAZARD-PHAROS ARMED-PHAROS ADMIN OVERRIDE`. #. Beacon stacks show :orange:`orange` and :blue:`blue` LEDs on. - Vault-1 Control - Vault-1 east wall - Pharos LASER ENCLOSURE INTERLOCK protocase #. Beacon stack on Dira LASER ENCLOSURE INTERLOCK protocase only shows :blue:`blue` LED on. #. Arm the LOCAL INTERLOCK CONTACT CONTROL modules on the Pharos LASER ENCLOSURE INTERLOCK protocase. - CONTROL #1 - CONTROL #2 #. With the Pharos, Vault-1, and LOCAL INTERLOCK CONTACT CONTROL modules armed and the Pharos enclosure set to override, open one of the Pharos enclosure rolling doors. In response: - Pharos LASER ENCLOSURE INTERLOCK protocase laser warning module will display :red:`LASER ON`. - The LOCAL INTERLOCK CONTACT CONTROL modules will stay armed. - Pharos LASER ENCLOSURE INTERLOCK protocase door monitor will display :green:`CLOSED`. - Pharos UV and IR shutters will not close. - The Pharos power supply stays on. #. Turn the Pharos LASER ENCLOSURE INTERLOCK protocase INTERLOCK OVERRIDE key from :red:`OVERRIDE` to :red:`INTERLOCK`. The STATUS LED changed to :green:`green`. The VIEWMARQ display and beacon stacks show a non-override status. .. figure:: /images/testing_documentation/Vault-1_laser/Vault-1_Control_VIEWMARQ_Pharos_override.jpg :align: center :scale: 20 % **Figure 14:** This is the Vault-1 Control VIEWMARQ display when the system is overridden. .. figure:: /images/user_docs/Vault-1_laser/Pharos_protocase_override.jpg :align: center :scale: 20 % **Figure 15:** This is the Pharos LASER ENCLOSURE INTERLOCK protocase when the system is overridden. ----- Arming the Dira Enclosure and Laser ----------------------------------- #. Disarm Vault-1 and the Pharos. #. See Laser Lab testing procedure for arming the Dira. The laser warning module on Dira enclosure displays :red:`DANGER LASER ON`. #. Change the Dira LASER ENCLOSURE INTERLOCK protocase INTERLOCK OVERRIDE key from INTERLOCK to OVERRIDE. The STATUS LED remains :green:`green`. Change back to INTERLOCK. ----- Administrative Override on the Dira Enclosure --------------------------------------------- #. Open the Dira enclosure rolling doors. In response: - Dira and Pharos LASER ENCLOSURE INTERLOCK protocase laser warning module will display :green:`LASER SAFE` - The LOCAL INTERLOCK CONTACT CONTROL modules will disarm and display :orange:`LOCAL CONTACTS DISARMED` on the Dira and Pharos protocases. - Dira and Pharos LASER ENCLOSURE INTERLOCK protocase door monitor will display nothing. - Pharos UV and IR shutters will close. - Dira UV and IR shutters will close. - The Dira power supply is cut off. - The Pharos power supply is cut off. #. Rearm the Dira. #. With Vault-1, the Dira armed, and the Pharos armed turn the INTERLOCK OVERRIDE key on the Dira LASER ENCLOSURE INTERLOCK protocase from :red:`INTERLOCK` to :red:`OVERRIDE`. The STATUS LED will change to :red:`red`. #. The VIEWMARQ displays :red:`DANGER LASER HAZARD-PHAROS ARMED-DIRA ARMED-DIRA ADMIN OVERRIDE`. #. Beacon stacks show :orange:`orange`, white, and :blue:`blue` LEDs on. - Vault-1 Control - Vault-1 east wall - Dira LASER ENCLOSURE INTERLOCK protocase. #. Beacon stack on the Pharos LASER ENCLOSURE INTERLOCK protocase will show :blue:`blue` LEDs on. #. Turn the INTERLOCK OVERRIDE key on the Pharos LASER ENCLOSURE INTERLOCK protocol case from :red:`INTERLOCK` to :red:`OVERRIDE`. The STATUS LED will change to :red:`red`. #. The VIEWMARQ in Vault-1 Control will display :red:`DANGER LASER ON - PHAROS ARMED - DIRA ARMED - PHAROS ADMIN OVERRIDE - DIRA ADMIN OVERRIDE`. #. The beacon stack on the Pharos LASER ENCLOSURE INTERLOCK protocase will show :orange:`orange` and :blue:`blue` LEDs on. #. With the Pharos, Dira, Vault-1, and LOCAL INTERLOCK CONTACT CONTROL armed and the Dira and Pharos enclosures set to override, open one of the Dira enclosure rolling doors. In response: - Pharos LASER ENCLOSURE INTERLOCK protocase laser warning module will display :red:`DANGER LASER ON` - The LOCAL INTERLOCK CONTACT CONTROL modules will disarm on the Pharos. - Pharos UV and IR shutters will not close. - Dira UV and IR shutters will not close. #. With the Pharos, Dira, and Vault-1 armed and the Dira and Pharos enclosures set to override, open one of the Dira enclosure rolling doors. In response: - Dira LASER ENCLOSURE INTERLOCK protocase warning module will display :red:`DANGER LASER ON`. - Dira LASER ENCLOSURE INTERLOCK protocase door monitor will display :red:`CLOSED`. - Pharos LASER ENCLOSURE INTERLOCK protocase door monitor will display nothing. - Pharos UV and IR shutters will close. - Dira UV and IR shutters will close. .. figure:: /images/user_docs/Vault-1_laser/Vault-1_VIEWMARQ_all_armed.jpg :align: center :scale: 20 % **Figure 16:** This is the Vault-1 Control VIEWMARQ display when the system is overridden. .. figure:: /images/user_docs/Vault-1_laser/Dira_protocase_override.jpg :align: center :scale: 20 % **Figure 17:** This is the Dira LASER ENCLOSURE INTERLOCK protocase when the system is overridden. ----- Crashing the Dira Laser ------------------------- #. Once every 6 months, the Pharos laser emergency stop buttons are tested that they can successfully cut power to the Pharos from a functional state. Verify if the last testing date was 6 months ago. #. If 6 months have passed, arm the Pharos laser, and use one of the laser e-stops to crash the laser and verify that power has been cut. ----- Return to Starting Conditions ----------------------------- #. Return the Vault-1 laser interlock system back to starting conditions.